Honeywell 900A16-0301 Analog Input Module
Honeywell 900A16-0301 Analog Input Module
Manufacturer: Honeywell
-
Product No.: 900A16-0301
Condition:in Stock
Product Type: Analog Input Module
-
Product Origin: USA
Payment:T/T, Western Union
-
Weight: 1000g
Shipping port: Shanghai/Yiwu/Shenzhen
Warranty: 12 months
Share
Honeywell 900A16-0301 High-Level Analog Input Module
The 900A16-0301 is a 16-channel high-level analog input (HLAI) module developed by Honeywell for the ControlEdge HC900 modular controller family. Designed for high-density analog data acquisition, it connects field transmitters—such as flowmeters, pressure sensors, and temperature transmitters—directly to the controller backplane for process monitoring and closed-loop control.
Signal Processing and Switch-Selectable Shunts
The module processes voltage input ranges including 0 to 1 VDC, 0 to 2 VDC, 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, and bipolar ranges up to ±10 VDC. For 0 to 20 mA and 4 to 20 mA current loops, integrated 250 Ω shunt resistors can be engaged via DIP switches, eliminating the need for external precision resistors. An onboard 15-bit A/D converter delivers ±0.1% full-scale accuracy with a module update rate of 100 ms across all 16 channels.
System Isolation and Installation Requirements
To safeguard system logic against severe electrical noise and common-mode transients, the module features galvanic isolation rated at 400 VDC channel-to-channel and 1000 VDC channel-to-logic. The module plugs directly into any standard HC900 I/O rack slot and connects to field wiring using a 36-terminal Euro-style terminal block (Model 900TEK-0301 or equivalent). It operates from an internal 5 VDC bus drawing up to 250 mA, with safety certifications for CE, UL/cUL, FM Class I Div 2, and ATEX Zone 2 environments.
| Parameter | Specification |
|---|---|
| Model | 900A16-0301 |
| Brand | Honeywell |
| Product Type | High-Level Analog Input Modules |
| System Compatibility | ControlEdge HC900 |
| Channel Count | 16 channels |
| Input Ranges (Voltage) | 0 to 1 VDC, 0 to 2 VDC, 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, +/-1 VDC, +/-2 VDC, +/-5 VDC, +/-10 VDC |
| Input Ranges (Current) | 0 to 20 mA, 4 to 20 mA (DIP-switch selectable 250 ohm internal shunts) |
| A/D Converter Resolution | 15 bit |
| Module Update Rate | 100 ms (all 16 channels) |
| Galvanic Isolation | 400 VDC channel-to-channel, 1000 VDC channel-to-logic |
| Input Impedance | > 10 Mohms (voltage), 250 ohms (current via internal shunt) |
| Accuracy | +/-0.1% full scale (under calibrated conditions) |
| Power Consumption | 250 mA max @ 5 VDC |
| Required Terminal Block | 36-terminal Euro-style (Model 900TEK-0301) |
| Operating Temperature | 0 deg C to 60 deg C (32 deg F to 140 deg F) |
| Storage Temperature | -40 deg C to 85 deg C (-40 deg F to 185 deg F) |
| Relative Humidity | 5% to 95% RH (non-condensing) |
| Certifications & Approvals | CE, UL/cUL, FM Class I Div 2, ATEX Zone 2 |
Frequently Asked Questions
Q: How are current signals configured on the Honeywell 900A16-0301 module? A: Current loops (0–20 mA or 4–20 mA) are selected via internal DIP switches that engage built-in 250 Ω shunt resistors on each channel.
Q: What terminal block model is required for field wiring? A: The module requires a 36-terminal Euro-style block, specifically Honeywell part number 900TEK-0301 or an equivalent compatible block.
Q: What isolation protection is provided between channels and controller logic? A: It provides 400 VDC channel-to-channel isolation and 1000 VDC galvanic isolation between the field channels and the internal logic backplane.