Honeywell
📢 100% genuine, extensive in-stock inventory, fast shipping!
Honeywell 900B01-0001 Analog Output Module
Honeywell 900B01-0001 Analog Output Module
Manufacturer: Honeywell
-
Product No.: 900B01-0001
Condition:in Stock
Product Type: Analog Output Module
-
Product Origin: USA
Payment:T/T, Western Union
-
Weight: 408g
Shipping port: Shanghai/Yiwu/Shenzhen
Warranty: 12 months
Share
Honeywell 900B01-0001 Analog Output Module
Configured for analog signal output generation in Honeywell control systems, the Honeywell 900B01-0001 (900B01-0001 Analog Output Module) provides direct electrical output through four isolated analog channels. The module converts controller data into field-level current signals for interfacing with final control elements, recorders, and process instrumentation.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 900B01-0001 |
| Brand | Honeywell |
| Product Type | Analog Output Module |
| Number of Channels | 4 isolated channels |
| Signal Range | 0 mA to 21.8 mA, configurable to 4 mA to 20 mA |
| D/A Resolution | 12 bits |
| Calibrated Accuracy | +/-0.1% of full scale at 25 deg C |
| Maximum Load Resistance | 750 Ohm |
| Update Rate | Synchronous with controller scan cycle |
| Diagnostics | Minimum current sensing, built-in fault detection |
| 5 VDC Loading | 40 mA maximum |
| 24 VDC Loading | 200 mA maximum |
| Channel-to-Channel Isolation | 500 VDC |
| Field-to-Logic Isolation | 600 VDC |
| Dimensions | 137 mm x 35.6 mm x 66 mm |
| Weight | Approximately 0.408 kg |
| Operating Temp | 0 deg C to 60 deg C |
| Storage Temp | -40 deg C to 70 deg C |
| Operating Humidity | 10% to 90% RH, non-condensing |
| Environmental Protection | G3 conformal coating |
| Power Consumption | 5 VDC 40 mA max, 24 VDC 200 mA max |
Channel-to-Channel Isolation and Analog Signal Integrity
The 900B01-0001 incorporates four electrically isolated analog output channels designed to reduce interaction between independently controlled output loops. Channel-to-channel isolation is rated at 500 VDC, while field-to-logic isolation is rated at 600 VDC.
The module supports configurable current output operation, including standard 4 mA to 20 mA process control loops. Galvanic isolation assists in reducing the effects of ground potential differences and field wiring disturbances between output circuits and controller electronics.
Built-in output diagnostics continuously monitor channel operation and provide fault detection capability. Minimum current sensing functions support verification of output loop integrity during operation.
Frequently Asked Questions
Q: Does the module support standard 4 mA to 20 mA control loops?
A: Yes. The output range is user-configurable and supports standard 4 mA to 20 mA analog current applications.
Q: What is the maximum field load supported by each output channel?
A: Each output channel supports load resistance up to 750 Ohm.
Q: Are the output channels electrically isolated from one another?
A: Yes. The module provides 500 VDC channel-to-channel galvanic isolation and 600 VDC field-to-logic isolation.
Field Installation Guidelines
-
Verify controller and backplane compatibility before installing the module.
-
De-energize the I/O chassis before inserting or removing the module unless site procedures specifically permit online maintenance.
-
Route analog output wiring separately from AC power and motor circuits.
-
Use shielded instrumentation cable for low-noise analog signal transmission where required by site standards.
-
Terminate cable shields according to plant grounding practices to avoid ground loop conditions.
-
Confirm field load resistance does not exceed the specified 750 Ohm limit.
-
Verify output scaling and loop calibration after installation and before placing the control loop into service.